Troubleshooting your system
Select the problem you're having from the following list
Problem: Compressor will not run
POSSIBLE CAUSES | POSSIBLE CORRECTIVE STEPS | |
---|---|---|
1. Main switch open. | 1. Close switch. | |
2. Fuse blown. | 2. Check electrical circuits and motor winding for shorts or grounds. Investigate for possible overloading. Replace fuse after fault is corrected. | |
3. Thermal overloads tripped. | 3. Overload are automatically reset. Check unit closely when unit comes back on line. | |
4. Defective contactor or coil. | 4. Repair or replace. | |
5. System shut down by safety switch | 5. Determine type and cause of shutdown and correct it before resetting safety switch. | |
6. No cooling required. | 6. None. Wait until calls for cooling. | |
7. Liquid line solenoid will not open | 7. Repair or replace coil. | |
8. Motor electrical trouble. | 8. Check motor for open windings, short circuit or burn out. | |
9. Loose wiring. | 9.Check all wire junctions. Tighten all terminal screws. |
Problem: Compressor noisy or vibrating
POSSIBLE CAUSES | POSSIBLE CORRECTIVE STEPS | |
---|---|---|
1. Flooding of refrigerant into crankcase. | 1. Check setting of expansion valves. | |
2. Improper piping support on suction or liquid line. | 2. Relocate, add or remove hangers. | |
3. Worm compressor. | 3. Replace. |
Problem: High discharge pressure
POSSIBLE CAUSES | POSSIBLE CORRECTIVE STEPS | |
---|---|---|
1. Non-condensable in system. | 1. Remove the non-condensable. | |
2. System overcharges with refrigerant. | 2. Remove excess. | |
3. Discharge shutoff valve partially closed. | 3. Open valve. | |
4. Fan not running. | 4. Check electrical circuit. | |
5. Head pressure control setting. | 5. Adjust. | |
6. Dirty condenser coil. | 6. Clean. |
Problem: Low discharge pressure
POSSIBLE CAUSES | POSSIBLE CORRECTIVE STEPS | |
---|---|---|
1. Faulty condenser temperature regulation. | 1. Check condenser control operation. | |
2. Suction shutoff valve partially closed. | 2. Open valve. | |
3. Insufficient refrigerant in system. | 3. Check for leaks. Repair and add charge. | |
4. Low suction pressure. | 4. See corrective steps for low suction pressure. | |
5. Variable head pressure valve. | 5. Check valve setting. |
Problem: High suction pressure
POSSIBLE CAUSES | POSSIBLE CORRECTIVE STEPS | |
---|---|---|
1. Excessive load. | 1. Reduce load or add additional equipment. | |
2. Expansion valve overfeeding. | 2. Check remote bulb. Regulate superheat. |
Problem: Low suction pressure
POSSIBLE CAUSES | POSSIBLE CORRECTIVE STEPS | |
---|---|---|
1. Lack of refrigerant. | 1. Check for leaks. Repair and add charge. | |
2. Evaporator dirty or iced. | 2. Clean. | |
3. Clogged liquid line filter drier. | 3. Replace cartridge(s). | |
4. Clogged suction line or compressor suction gas strainers. | 4. Clean strainers. | |
5. Expansion valve malfunctioning. | 5. Check and reset for proper superheat. | |
6. Condensing temperature too low. | 6. Check means for regulating condensing temperature. | |
7. Improper TXV. | 7. Check for proper sizing. |
Problem: Little or no oil pressure
POSSIBLE CAUSES | POSSIBLE CORRECTIVE STEPS | |
---|---|---|
1. Clogged suction oil strainer. | 1. Clean. | |
2. Excessive liquid in crankcase. | 2. Check crankcase heater. Reset expansion valve for higher superheat. Check liquid line solenoid valve operation. | |
3. Low oil pressure safety switch defective. | 3. Replace. | |
4. Worm oil pump. | 4. Replace. | |
5. Oil pump reversing gear stuck in wrong position. | 5. Reverse direction of compressor rotation. | |
6. Worn bearings. | 6. Replace compressor. | |
7. Low oil level. | 7. Add oil and/or through defrost. | |
8. Loose fitting on oil lines. | 8. Check and tighten system. | |
9. Pump housing gasket leaks. | 9. Replace gasket. |
Problem: Compressor loses oil
POSSIBLE CAUSES | POSSIBLE CORRECTIVE STEPS | |
---|---|---|
1. Lack of refrigerant. | 1. Check for leaks and repair. Add refrigerant. | |
2. Excessive compression ring blow by | 2. Replace compressor | |
3. Refrigerant flood back. | 3. Maintain proper superheat at compressor. | |
4. Improper piping or traps. | 4. Correct piping. |
Problem: Compressor thermal protector switch open
POSSIBLE CAUSES | POSSIBLE CORRECTIVE STEPS | |
---|---|---|
1. Operating beyond design conditions. | 1. Add facilities so that conditions are within allowable limits. | |
2. Discharge valve partially shut. | 2. Open valve. | |
3. Blown valve plate gasket. | 3. Replace gasket. | |
4. Dirty condenser coil. | 4. Clean coil. | |
5. Overcharged system. | 5. reduce charge. |